THREE-PHASE ELECTRIC ENERGY METER SEA3.
Purpose
Accounting of electric energy on single-tariff in three phase three- or four-wire AC chains directly or through measuring current transformers, stand-alone or with informing-measuring systems as an energy gain and power measuring units. Three-phase, static, electronic electric energy meters SEA33 are electro technical devices constitutes itself analogue-digital units realizing summing up and indication on lector-mechanical counting device or electronic display the quantity of consumed power directly in kWt/h.
Application field
In consumer and industrial sector in electric energy consumption in three-phase electric chain (industrial companies, residual and public buildings, portable constructions, cottages, country houses, garages etc.)
Regulatory
Meters correspond following requirements:
GOST R 52320 – 2005 (MEK 62052 – 11: 2003);
GOST R 52322 – 2005 (MEK 62053 – 21: 2003);
Technical conditions IZHSK. 411152.003 TU and safety requirement, specified in GOST R 51350 – 99.
Included to State Register of measuring means of Russia after ¹ 18264 – 08.
Meters are certified.
Features
High sensitivity on load current.
Low self power consumption.
Standard telemetry impulse output.
Indicator of performance.
Possible modifications with mechanical counters and LED.
Protection from underestimation and electric energy stealing and waste.
Tolerance for climate, mechanical and electromagnetic influence.
Reliability features
Mean time to failure – not less then 90000 hours.
Calibration interval – 10 years
Mean lifetime – 30 years.
Warranty lifetime – 18 months
Operation conditions
Meters are to be mounted inside the buildings and devises of outside installation which can provide IP33 protection level with operating conditions as follows:
ambient temperature from minus 40°Ñ up to +60°Ñ for meters with mechanical counter and from minus 20°Ñ up to +60°Ñ for meters with LED.
relative humidity 98% with +25°Ñ
atmospheric pressure from 537 up to 800 Torr
Convention structure
Technical characteristics
Number of tariffs |
1 |
Accuracy class according GOST R 52323-2005 |
0,5S |
Measuring net frequency, Hz |
50 ± 2% |
Nominal voltage, V |
3õ100; 3x57,7/100; 3x230/400 |
Nominal (maximal) current, A |
1 (1,5); 5 (7,5) |
Starting current (sensitivity), % from 1 nom |
0,1 |
Total (active) consumed power of parallel circuit , not more then, V•A (Wt) |
8 (2) |
Total consumed power of sequencing circuit, not more then, V•A (Wt) |
0,1 |
Working temperatures range, °C |
îò -40 äî +60 |
Weight, not more then, kg |
2,0 |
Body modification
Indication |
Modification |
Nominal voltage, V |
Nominal current, A |
Gear ratio of impulse output unit, imp/kWt.h |
SEA33MU 5-7,5A |
transformer
three-wire
double-element
small-size |
3õ100 |
5(7,5) |
16000 |
SEA33MU 1-1,5A |
1(1,5) |
80000 |
SEA33M 5-7,5A |
transformer
four-wire
small-size |
3õ230/400 |
5(7,5) |
1600 |
SEA33M 1-1,5A |
1(1,5) |
16000 |
SEA33MT 5-7,5A |
3õ57,7/100 |
5(7,5) |
16000 |
SEA33MT 1-1,5A |
1(1,5) |
80000 |
SEA33MUI 5-7,5A |
transformer
three-wire
double-element
small-size |
3õ100 |
5(7,5) |
16000 |
SEA33MUI 1-1,5A |
1(1,5) |
80000 |
SEA33MI 5-7,5A |
transformer
four-wire
small-size |
3õ230/400 |
5(7,5) |
1600 |
SEA33MI 1-1,5A |
1(1,5) |
16000 |
SEA33MTI 5-7,5A |
3õ57,7/100 |
5(7,5) |
16000 |
SEA33MTI 1-1,5A |
1(1,5) |
80000 |
Overall and mounting dimensions of SEA33 meter

Weight not more then 2 kg.
Clamps marking and meter switch-on scheme

Switch-on scheme of four-wire transformer on current meters (SEA33M, SEAMI)

Switch-on scheme of three-wire transformer on current and voltage meters (SEA33MU, SEAMUI)

Switch-on scheme of four-wire transformer on current and voltage meters (SEA33MT, SEAMTI)
Indication in the order
SEA33MU 5-7,5A IZHSK. 411152.007TU: Electric energy meter three-wire, transformer switch-on on current and voltage with nominal current of 5A, nominal voltage of 3õ100Â and mechanical counter.
SEA33MI 1-1,5A IZHSK. 411152.007TU: Electric energy meter four-wire, transformer switch-on on current with nominal current of 1A, nominal voltage of 3õ230/400 and LED.
|
|