THREE-PHASE ELECTRIC ENERGY METER SEA3.
Three-phase electric energy meter SEA3 is an electrotechnical product, analog-digital devise that sums and indicates on electromechanical reading device the quantity of electric energy meter input in kWt/h.
General purpose
Measuring of active electric energy by one or two rates in tree- or four-wire three-phase circuits directly or through measuring current and voltage transformers, autonomously or amounting to information and metering systems as a sensor of energy increment and power measuring.
Standard provision
The meters are developed and go into series production according to the requirements of Quality standard ISO 9001 (GOST R ISO 9001-2001), correspond to technical specifications IZHSK. 411152.003 TU, GOST 30207-94 “Static meters of active energy Watt-hours of alternating current (accuracy class 1-2)”, safety requirements determined by GOST R 51350-99. The meters are included in public register of measurement instrumentation in Russia, reference No18264-04, and several countries of the CIS. The meter is certified. Certificate of conformance No 6526270.
Features
The meters are made on the basis of specialized microcircuit by means of surface mounting technology.
The meters have large technological margin on accuracy class.
Stable to mechanical and climatic influence.
Stable to fails and short breaks of mains supply voltage.
The meters correspond to the requirements to products on electromagnetic compatibility.
The meters are protected from shunt running and influence of constant and alternating external electromagnetic fields.
The meters have impulse telemetering output and indicator lamp that operates as indicator of voltage presence in the circuit as well as indicator of a consumer’s load.
Double-rate modification has an input for switching the tariff.
Reliability characteristics
Mean time to failure – 72000 hours.
Mean lifetime – 25 years.
Warranty lifetime – 18 months.
Calibration interval – 6 years.
Construction
The meter is made in a plastic case, protection from dust and water penetration - IP 51. The case comprises a meter block consisting of terminal block with two or three measuring current transformers, printed-circuit board with surface and volumetric mounting of electronic components and reading devise. Terminal block has a sealed lid. Meter case is sealed by the division of technical control of the manufacturing plant and by a state officer.
Modifications
| № |
Name |
Modification |
Accuracy class |
Type of reading device indicator |
Way of switching summators of tariff II into active state (for double-rate meters) |
| 1 |
SEA3-1 5-55A |
Single-rate of direct connection |
2 |
Mechanical |
|
| 2 |
SEA3М-1 5-55А* |
| 3 |
SEA3М-1 5-55А 1,0* |
1 |
| 4 |
SEA3МI-1 5-55А 1,0* |
LCD |
| 5 |
SEA3-1 10-100А |
2 |
Mechanical |
| 6 |
SEA3-1 1-8А |
Single-rate, connected through measuring current transformers |
| 7 |
SEA3М-1 1-8А* |
| 8 |
SEA3М-1 1-8А 1,0* |
1 |
| 9 |
SEA3МI-1 1-8А 1,0* |
LCD |
| 10 |
SEAМТ-1 1-8А* |
Single-rate, connected through measuring current and voltage transformers |
2 |
Mechanical |
| 11 |
SEA3МТ-1 1-8А 1,0* |
1 |
| 12 |
SEA3МТI-1 1-8А 1,0* |
LCD |
| 13 |
SEA3МУ-1 1-8А 1,0* |
Mechanical |
| 14 |
SEA3МUI-1 1-8А 1,0* |
LCD |
| 15 |
SEA3-2 5-55А |
Double-rate of direct connection |
2 |
Mechanical |
Tariffs can be switched by means of any external tarifficator ensuring control voltage supply of the required value (~220 V, frequency 50 Hz or +12 V of direct current). |
| 16 |
SEA3М-2 5-55А* |
| 17 |
SEA3-2 10-100А |
| 18 |
SEA3МI-2 5-55А 1,0* |
1 |
LCD |
| 19 |
SEA3-2 1-8А |
Double-rate, connected through measuring current and voltage transformers |
2 |
Mechanical |
| 20 |
SEA3М-2 1-8А* |
| 21 |
SEA3МI-2 1-8А 1,0 |
1 |
LCD |
| 22 |
SEA3МТ-2 1-8А* |
2 |
Mechanical |
| 23 |
SEA3МТИ-2 1-8А* 1,0* |
1 |
LCD |
| 24 |
SEA3МУ-2 1-8А* |
2 |
Mechanical |
| 25 |
SEA3МUI-2 1-8А 1,0* |
1 |
LCD |
* designed in a small-size case.
** double-rate meters in which summators are switched by means of direct current, in the end of its name index +12V is added
Технические характеристики
| Parameters name |
Parameters value |
| Rated voltage, V |
3х220/280 with 1 - 16 pos., 3х57,7/100 with 17 - 21 pos., 3х100 with 22 - 25 pos. |
| Rated (maximum) current, A |
5(55) with 1 - 7 pos., 10(100) with 8 - 9 pos., 1(8) with 10 - 25 pos. |
| Frequency of measuring circuit, Hz |
50±2,5 |
| Established voltage working range, V |
198-242 with 1 - 16 pos., 52-63,5 with 17 - 21 pos., 90-110 with 22 - 25 pos. |
| Limiting voltage working range, V |
176-253 with 1 - 16 pos., 46-66,4 with 17 - 21 pos., 80-115 with 22 - 25 pos |
| Range of measured currents, A |
0,5-55 with 1-7 pos., 1-100 with 8-9 pos., 0,1-8 with 10 по 25 pos. |
| Threshold of sensitivity, Wt, not more than |
16,5 with 1-7 pos., 33 with 8-9 pos., 3,3 with 10 по 16 pos., 0,9 with 17 - 25 pos. |
| Gear-ratio of transmitting terminal, imp./ kWt.h |
1600 with 1 - 9 pos., 16000 with 10 - 25 pos. |
| Weight, kg, not more than |
2 |
Marks of clips and schemes of inclusion of counters
Overall and mounting dimensions of meters SEA3
Overall and mounting dimensions of meters SEA3M
|
|